Descrizione
Download Datasheet
Download User Manual
The DEYE SUN-80K-G03 converts the energy generated by photovoltaic panels into three-phase electrical energy compatible with 380/400V utility grids. Its rated output power of 80kW makes it suitable for large commercial and industrial installations.
The maximum supported photovoltaic power is 104kW. Its four MPPT trackers, each with four string inputs, provide flexible PV array connection and management, including installations where groups of panels have different orientations or irradiation conditions.
The MPPT operating range is 200–850V, while the maximum input voltage is 1000V. The maximum operating current is 40A per MPPT, while the maximum short-circuit current is 60A per MPPT.
The inverter offers a maximum efficiency of 98.7%, an IP65-rated enclosure and intelligent air cooling. RS485 and RS232 interfaces enable monitoring-system integration, while GPRS, Wi-Fi, Bluetooth, 4G or LAN connectivity is available through optional modules.
Key Features
- 80kW rated output power
- 88kVA maximum apparent power
- 104kW maximum photovoltaic power
- Four MPPT trackers
- 16 string inputs, with four inputs per MPPT
- 200–850V MPPT operating range
- 1000V maximum input voltage
- 40A + 40A + 40A + 40A maximum operating current
- 98.7% maximum efficiency
- 98.1% European efficiency
- IP65-rated enclosure
- Intelligent air cooling
- Type II DC and AC surge protection
- Zero Export function with compatible equipment
- Smart string monitoring – optional
- Anti-PID function – optional
Benefits
High Output for Commercial Applications
The 80kW rated output allows the inverter to be used in photovoltaic systems installed on industrial buildings, warehouses, manufacturing facilities and commercial buildings.
Flexible PV Array Management
The four MPPT trackers allow the panels to be divided into independently managed groups, helping optimise production when panel orientations or operating conditions differ.
Flexible DC-to-AC Ratio
The maximum photovoltaic power of 104kW allows the PV array to be larger than the inverter’s rated AC output, subject to the manufacturer’s limits and requirements.
Integrated Protection Functions
The inverter includes protection against DC reverse polarity, overcurrent, overvoltage, short circuits, excessive temperature, insulation faults, residual current and unintended island operation.
Remote Monitoring
The connectivity options enable production and operating parameters to be monitored through compatible platforms.
Recommended Applications
- Industrial buildings and premises
- Factories and manufacturing facilities
- Warehouses and logistics centres
- Commercial buildings
- Business centres
- Farms and agricultural facilities
- Commercial photovoltaic power plants
- Three-phase grid-connected systems
- Installations requiring energy export limitation
| General Information |
| Manufacturer |
DEYE |
| Model |
SUN-80K-G03 |
| V-TAC Product Code |
12724 |
| Inverter Type |
On-grid, three-phase |
| Topology |
Transformerless |
| Photovoltaic Input – DC |
| Maximum Photovoltaic Power |
104kW |
| Maximum Input Voltage |
1000V |
| Start-Up Voltage |
250V |
| Rated Input Voltage |
600V |
| MPPT Range |
200–850V |
| Maximum PV Operating Current |
40A + 40A + 40A + 40A |
| Maximum PV Short-Circuit Current |
60A + 60A + 60A + 60A |
| MPPT Trackers / Strings per MPPT |
4 / 4 + 4 + 4 + 4 |
| Grid Output – AC |
| Rated Active Power |
80kW |
| Maximum Apparent Power |
88kVA |
| Rated AC Voltage / Range |
220/380V or 230/400V; 0.85Un–1.1Un |
| Grid Connection |
3L+N+PE |
| Rated AC Current |
121.2A at 380V / 115.9A at 400V |
| Maximum AC Output Current |
133.3A at 380V / 127.5A at 400V |
| Rated Frequency / Range |
50Hz / 45–55Hz; 60Hz / 55–65Hz |
| Power Factor Range |
0.8 leading to 0.8 lagging |
| Total Harmonic Distortion (THDi) |
<3% |
| DC Current Injection |
<0.5% In |
| Efficiency |
| Maximum Efficiency |
98.7% |
| European Efficiency |
98.1% |
| MPPT Efficiency |
>99% |
| Protection |
| DC Reverse-Polarity Protection |
Integrated |
| AC Overcurrent and Overvoltage Protection |
Integrated |
| AC Short-Circuit Protection |
Integrated |
| Thermal Protection |
Integrated |
| Insulation Impedance Detection |
Integrated |
| DC Component Monitoring |
Integrated |
| Anti-Islanding Protection |
Integrated |
| Residual Current Detection |
Integrated |
| Surge Protection |
Type II DC / Type II AC |
| DC Switch |
Integrated |
| AFCI Protection |
Optional |
| General Characteristics |
| Ingress Protection Rating |
IP65 |
| Operating Temperature |
-25°C to +60°C, with power derating above +45°C |
| Permissible Humidity |
0–100% |
| Maximum Altitude |
4000m |
| Noise Level |
≤55dB |
| Cooling |
Intelligent air cooling |
| Dimensions |
824 × 516 × 312.7mm, excluding connectors and mounting brackets |
| Weight |
81kg |
| Overvoltage Category |
OVC II DC / OVC III AC |
| Communication and Compliance |
| Communication Interfaces |
RS485 / RS232 |
| Optional Monitoring |
GPRS, Wi-Fi, Bluetooth, 4G or LAN |
| Referenced Grid Standards |
IEC 61727, IEC 62116, CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002, G99, VDE-AR-N 4105 |
| Safety and EMC Standards |
IEC/EN 62109-1/-2, IEC/EN 61000-6-1/2/3/4 |
| Warranty |
5 years |
Compatibility and Important Information
This is an on-grid inverter. It does not have a battery input and does not provide backup power when the utility grid is unavailable.
The Zero Export function requires a compatible meter or metering system that has been correctly installed and configured.
Smart string monitoring, Anti-PID, AFCI protection and wireless communication modules are optional. Their inclusion must be checked in the supplied commercial configuration.
The maximum photovoltaic power of 104kW must not be confused with the rated AC output power of 80kW.
The PV strings must be sized according to the panels’ Voc, Vmp, Isc and Imp values, the limits of each MPPT tracker and the minimum and maximum temperatures at the installation site.
Compatibility with the distribution system operator’s requirements and the regulations applicable to the project must be checked before purchase.
Installation, configuration and commissioning must be carried out by qualified personnel in accordance with the manufacturer’s instructions and all applicable regulations.